SEALED LEAD ACID BATTERIES - TERMINALS, CHARGING & APPLICATION NOTES
CHARGING SLA BATTERIES

If you can't find the battery you are looking for, fill out the form below to enquire about our range of Sealed Lead Acid Batteries and we will get back to you as soon as possible.

Your details were sent successfully!

Cycle Applications:

Limit initial current to 0.30C (C is the nominal A.H. capacity of the battery). Charge until battery voltage (under charge) reaches 2.45 volts per cell at 68 degrees F (20 degrees C). Hold at 2.45 volts per cell until current drops to approximately 0.01C amperes. Battery is fully charged under these conditions, and charger should be disconnected or switched to "float" voltage.

"Float" or "Standy-by" Service:

Hold battery across constant voltage source of 2.25 to 2.30 volts per cell continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.

APPLICATION NOTES

Continuous over or undercharging is the single worst enemy of a lead-acid battery. Caution should be exercised to insure that the charger is disconnected after cycle charging, or that the float voltage is set correctly.

 

Because there is a chance of off-gassing dydrogen and oxygen if the battery is overcharged, it is important to provide adequate air circulation.

 

Batteries should not be stored in a discharged state (or in a hot place). If a battery has been discharged for some time it may not readily take a charge. To over-come this, leave the charger connected and the battery will eventually begin to accept a charge.

 

Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged after 6 months of storage at 20-25 degrees C, otherwise permanent loss of capacity might occur as a result of sulfation. To prolong shelf life without charging, store batteries at 50 degrees F (10 degrees C) or less.